Cut to length - sold by the foot. Enter desired footage in QTY box.
Minimum 50' maximum 1000'. Please call for different colors or longer put ups.
Applications:
TelcoFlex® II Central Office Power Wire and Cable Class I Flexible Tinned Strand Without Braid. has low-smoke, lead-free silicone-free non-halogenated insulation. UL 105ºC dry, 60ºC wet. Listed RHH/LS FT4 VW-1, 90ºC wet, 600 volts. Sizes 1/0 larger are UL, CT USE rated. CSA AWM B 105ºC, volts.
Specifications:
Meets exceeds following:
As: Cable
Standard 44: Thermoset Insulated Type RHH/ST1
FT-4 Flame Test
VW-1
ASTM B-33 B172 Strand
Physical Electrical tests accordance with 44 Requirements
105ºC
GR 347 Core Compliant Telcordia
Requirements of WP93811 Cold Flow (Creep) Cut Through
Non-Halogen
Low Smoke LS
IEC 60674 60332
RoHS / Reach Compliant
Construction:
Southwire's TelcoFlex ® is single conductor a (modified) bunched (8 6 AWG) rope-bunched (4 AWG larger) stranded copper conforming Underwriter's Laboratories requirements. An opaque mylar tape shall be applied over facilitate stripping. Insulation rated smoke, non-halogen, TelcoHyde™ 5221 Telcordia Specification GR-347-CORE, also limiting oxygen index 35%.
Conductors:
modified tin-coated Underwriters' stripping.
Insulation:
non-halogen 44, Subjects 509 758, C22.2 No. 210.2 M90. addition, complies GR-347-CORE. Surface Marking:
Two sides printed using ink contrasting color following information: "SOUTHWIRE (R) II/ KS24194 (TM) L2 NON-HAL (UL) E18321 _ VOLTS RHH ST1 3578 60(D)C WET VW-1 --- LL8825 105(D)C FT4-ST1 YEAR TIME JULIAN DATE INCLUDING & 60332 SEQUENTIAL MARKS"
Add "FOR USE" before "(UL)" on larger. markings at 2 foot intervals one side cable. manufacturing order number.
Specifications*:
Size: 10 AWG
Conductor Strand: 104
Insulation Thickness: 0.045 inches
Outside Diameter: 0.209 Weight: 0.059 lbs per ft
Max. D.C. Res. @ 20ºC: 1.080
*Data provided this page subject change based manufacturers variances.
There are no reviews for this product.
No questions about this product.