Applications:
Type UF-B cable is generally used as feeder to outside post lamps, pumps, and other loads or apparatus fed from a distribution point in an existing building as specified in the 2011 National Electrical Code. UF-B cable may be used underground, including direct burial. Multiple conductor UF-B cable may be used for interior branch circuit wiring in residential or agricultural buildings at conductor temperatures not to exceed 90°C (with ampacity limited to that for 60°C conductors) as specified by the National Electrical Code. UF-B can be used in applications permitted for NMC in Section 334.10(B) of the National Electrical Code. Voltage rating for UF-B cable is 600 volts.
Standards:
ASTM - B3 and B-8
UL Standard 83
UL Standard 493
Federal Specification A-A-59544
National Electrical Code, NFPA 70, 2011 Edition
RoHS/ REACH
Construction:
Conductors:
Stranded annealed soft bare copper per ASTM B3 and ASTM B8.
Insulation:
Polyvinyl chloride (PVC) with a nylon covering. Color coded phase identification.
Ground:
Soft bare copper, stranded per ASTM B3 and ASTM B8.
Jacket:
Sunlight, moisture and fungus resistant gray PVC.
Specifications*:
Size: 6 AWG
Number of Conductors: 2
PVC Insulation Thickness: 0.035 inches
Ground Wire Size: 10 AWG
Nylon Thickness: 0.005 inches
Nominal Cable Dimensions: .73 inches x .338 inches
Weight per foot: 0.303 lbs
Allowable Ampacity: 55 Amps
*Data provided on this page is subject to change based on different manufacturers variances.