Spec Sheet
Features
- Zero water peak single-mode fiber
- Maximizes support for lowest cost CWDM technology and delivers lowest cost path to future single-mode applications
- Supports legacy single-mode equipment and applications
Specification Description
Item: Plenum DistributionCable
Construction Type: Non-Armored
Fiber Type Solution: TeraSPEED Zero Water Peak Single-mode Fiber (G.652.D, G.657.A1)
Total Fiber Count: 12
Jacket Color: Aqua
Diameter Over Jacket: 0.23 Inch (5.77 mm)
Minimum Bend Radius: 3.4 Inch (8.6 cm) Loaded, 2.3 Inch (5.8 cm) Unloaded
Tensile Load: 45 lbf (200 N) Long Term, Maximum; 150 lbf (667 N) Short Term, Maximum
Vertical Rise: 500 m (1640.4 ft)
Environmental Space: Plenum
Installation Temperature: 0 to 70 deg C (32 to 158 deg F)
Operating Temperature: -20 to 70 deg C (-4 to 158 deg F)
Storage Temperature: -40 to 70 deg C (-40 to 158 deg F)
Compression: 10 N/mm (57 lb/Inch)
Flex: 100 Cycles
Impact: 4.34 ft lb (5.88 N-m)
Twist: 10 Cycles
Heat Age: -20 to 85 deg C (-4 to 185 deg F)
Low High Bend: -20 to 70 deg C (-4 to 158 deg F)
Temperature Cycle: -20 to 70 deg C (-4 to 158 deg F)
Includes: CS-8W-TB (Product Component-Not Orderable) TeraSPEED Single-mode Fiber
Tech Info
RoHS 2011/65/EU: Compliant; ISO 9001:2008: Designed, Manufactured and/or Distributed Under This Quality Management System; Flame Test Listing: NEC OFNP (ETL) and c(ETL), Flame Test Method: NFPA 262, Compression Test Method: FOTP-41, IEC 60794-1-2, Section 7; Flex Test Method: FOTP-104, IEC 60794-1-2, Section 10; Impact Test Method: FOTP-25, IEC 60794-1-2, Section 8; Strain Test Method: FOTP-33, IEC 60794-1-2, Section 5; Twist Test Method: FOTP-85, IEC 60794-1-2, Section 11; Low High Bend Test Method: FOTP-28, IEC 60794-1-2, Section 28; Temperature Cycle Test Method: FOTP-3, IEC 60794-1-2, Section 22; Cable Qualification Standards: ANSI/ICEA S-83-596-2001, Telcordia GR-409-CORE Issue 2