Cut to length - sold by the foot. Enter desired footage in QTY box.
Minimum 10' maximum 1000'. Please call for longer put ups.
Applications:
use power circuits up 8kV when installed open air, conduit, duct or buried directly earth, wet and dry locations. Used applications chemical plants, refineries, steel mills, industrial utility substations generating stations.
Jacket:
Black Polyvinylchloride (PVC) Jacket, sunlight resistant
Standards:
Listed as Type MV-105 per UL 1072 meets requirements of ICEA S-93-639. Sizes 1/0 larger marked "for CT use" pass 1685 70,000 Btu/hr flame test
Conductors:
Class B stranded, annealed, bare copper ASTM B-3 B-8, (compact stranding B-496 is available). Strand shield an extruded semi-conducting thermoset
Insulation:
Ethylene Propylene Rubber (EPR) S-93-639 (NEMA WC74)
Insulation Shield:
thermoset insulation shield. Metallic a helically applied 5 mil uncoated tape
Ampacity:
Based on three single conductor cables isolated conduit air NEC Table 310.73 with temperature 90°C ambient 40°C
Temperature: 105°C
Voltage: 5kV 133% 100%
Specifications*:
Conductors: 3 + 1 Ground
Size: 2 AWG
Ground Size: 6 Amps Conductor: 160
Jacket Thickness: 0.080 inches
Outside Diameter: 1.51 Weight: 1.51 lbs ft
*Data provided this page subject change different manufacturers variances.