Applications:
For use in power circuits up to 8 kV when installed open air, conduit, duct or buried directly the earth, wet and dry locations. Used applications chemical plants, refineries, steel mills, industrial utility substations generating stations.
Jacket:
Black Polyvinylchloride (PVC) Jacket, sunlight resistant
Standards:
Listed as Type MV-105 per UL 1072 meets requirements of ICEA S-93-639. Sizes 1/0 larger marked "for CT use" pass 1685 70,000 Btu/hr flame test
Conductors:
Class B stranded, annealed, bare copper ASTM B-3 B-8, (compact stranding B-496 is available). Strand shield an extruded semi-conducting thermoset
Insulation:
Ethylene Propylene Rubber (EPR) S-93-639 (NEMA WC74)
Insulation Shield:
thermoset insulation shield. Metallic a helically applied 5 mil uncoated tape
Ampacity:
Based on three single conductor cables isolated conduit air NEC Table 310.73 with temperature 90°C ambient 40°C
Temperature: 105°C
Voltage: 133% 100%
Specifications*:
Size: 2/0
Number Strands: 19
Insulation Thickness: 0.115 inches
Jacket 0.080 Outside Diameter: 0.960 Weight: 0.780 lbs ft
Amps Conductor: 205 amps
*Data provided this page subject change different manufacturers variances.
There are no reviews for this product.