Cut to length - sold by the foot. Enter desired footage in QTY box.
Minimum 20' maximum 1000'. Please call for longer put ups.
Applications:
use power circuits up 8 kV when installed open air, conduit, duct or buried directly earth, wet and dry locations. Used applications chemical plants, refineries, steel mills, industrial utility substations generating stations.
Jacket:
Black Polyvinylchloride (PVC) Jacket, sunlight resistant
Standards:
Listed as Type MV-105 per UL 1072 meets requirements of ICEA S-93-639. Sizes 1/0 larger marked "for CT use" pass 1685 70,000 Btu/hr flame test
Conductors:
Class B stranded, annealed, bare copper ASTM B-3 B-8, (compact stranding B-496 is available). Strand shield an extruded semi-conducting thermoset
Insulation:
Ethylene Propylene Rubber (EPR) S-93-639 (NEMA WC74)
Insulation Shield:
thermoset insulation shield. Metallic a helically applied 5 mil uncoated tape
Ampacity:
250 / 270 Duct, 345 385 Air
Temperature: 105°C
Voltage: 133% 100%
Specifications*:
Size: 3/0
Jacket Thickness: 0.080 inches
Outside Diameter: 0.963 Weight: 0.871 lbs ft
*Data provided on this page subject change based different manufacturers variances.