2/0 Stranded Aluminum Conductor 15KV URD, 133%, 1/3 Neutral
Cut to length - sold by the foot. Enter desired footage in QTY box.
Applications:
URD cable is primary used for underground distribution, direct burial or installed conduit. suitable use wet dry locations. be at 15,000 volts less and not exceed 90°C temperature normal use.
Conductor:
has a solid compressed concentric strand soft drawn 1350 series per ASTM.
Conductor Shield:
an extruded thermoset semiconducting shield, which free stripping from bonded insulation.
Insulation:
naturally high dielectric strength TR-XLPE insulation. There also insulation shield. Optional EPR available upon request.
Metalic neutral shield consisting of bare copper wires helically applied uniformly spaced over shield.
Jacket:
black jacket linear lows density polyethylene (LLDPE), sunlight, abrasion heat resistant. 3 red stripes, NESC lightning bolt sequential markings.
Standards:
ASTM B-3, B-8, B230, B-231, B-609 AEIC CS-8 ICEA S-94-649 T-31-610 T-34-664 continuous, 130°C emergency 250°C short-circuit operation
Specifications*:
Size: 2/0
Insulation Thickness: 220 mils
Concentric Neutral: 7-# 14
Conductor Diameter: 0.408 inches
0.89 0.96 Jacket 1.20 Cable Weight: 0.624 lbs ft
Ampacity: 90°C Duct = 186 amps 255 amps
*Data provided on this page subject change based different manufacturers variances.