Cut to length - sold by the foot. Enter the desired footage in the QTY box.
Minimum 50' to maximum 1000'. Please call for longer put ups.
Applications:
For use in power circuits up to 2,400 V where shields cannot be properly terminated and where space is limited. Cable is used for power applications in chemical plants, refineries, steel mills, industrial plants, utility substations and generating stations. Ideally suited for applications where increased durability is required.
Jacket:
TS - CPE - Thermoset Chlorinated Polyethylene
Standards:
Listed Type MV-90 per UL 1072 for wet and dry locations. Meets requirements of ICEA S-96-659 (NEMA WC71). Sizes 1/0 and larger marked Sunlight Resistant and pass IEEE 383 70,000 Btu/hr flame test and are marked "for CT use"
Conductors:
Class B stranded, annealed, bare copper per ASTM B-3 and B-8, strand shield is an extruded semiconducting compound per ICEA S-96-659 (NEMA WC71)
Insulation:
Ethylene Propylene Rubber (EPR) which meets or exceeds ICEA S-96-659 and UL 1072. For wet or dry locations per UL 1072 and NEC Article 328
Ampacity:
Based on three single conductor cables in isolated conduit in air per NEC Table 310.73 with a conductor temperature of 90°C and an ambient temperature of 40°C
Temperature:
90°C
Voltage:
2,400V
Specifications*:
Size: 350 MCM
Number of Strands: 37
Insulation Thickness: 0.140 inches
Jacket Thickness: 0.110 inches
Outside Diameter: 1.230 inches
Weight: 1.625 lbs per ft
Amps per Conductor: 385 amps
*Data provided on this page is subject to change based on different manufacturers variances.