Draka LMC044/0 Lifeline, 4/0-4C, MC, Two-Hour Fire Rated Cables
General Description
Lifeline MC fire resistive cables were designed to meet and have successfully passed the two-hour fire rating certification test per UL 2196, Standard for Tests for Fire Resistive Cables. Lifeline MC Cables are preferred over Mineral Insulated (MI) cables, concrete encasement or the construction of fire rated assemblies based on the facts that Lifeline MC Cables are less costly and easier to install for many applications. Fire resistive cables are required per NFPA 70, Articles 517, 695, 700, 708, 728 and 760 as well as NFPA 72 and NFPA 101.
Applications
- Emergency Feeder Cables
- Tall Buildings
- Stairwell Pressurization
- Elevators / OEO
- Fire Pumps
- Ventilating Fans
- Exit Lighting
- Emergency lighting for roadway and transmit tunnels when cables include optional LSZH jacket over armor
Specs and Ratings:
- Listed to UL 1569, Metal Clad Cables, as the following type:
- Type MC 600 Volt, Rated 90°C
- For Wet Locations
- For Cable Tray Use IEEE 1202/ FT4 Rated, ST1 Limited Smoke
- Classified to UL 2196, Standard for Tests for Fire Resistive Cables, for two-hours installations
- Electrical Circuit Integrity System (FHIT) No. 50 of the UL Fire Resistance Directory
- NFPA 70, NFPA 101 compliant
- Corrugated Copper Armor meets Equipment Grounding Conductor requirements of NEC Table 250.122
Conductor Size: 4/0 AWG
Conductors: 4
Conductor Material: Bare Stranded Copper
Insulation Material: Ceramifiable Silicone Zero Halogen (LSZH)
Outside Diameter: 2.28 Inches
Ampacity 75°C: 230
Ampacity 90°C: 260
Inner Binder Jacket: Ceramifiable Silicone Zero Halogen (LSZH)
Armor: Continuously Welded and Corrugated Copper
Net Weight: 2.80 lbs per ft
Spec Sheet
View Spec Sheet for Complete Details