$444.22
Estimated price. Final price and availability are subject to confirmation. Contact our sales team for a current quote.
The Square D IEC contactor TeSys Deca offers robust performance for industrial control applications. It is rated for 65A and capable of handling 40HP at 480VAC in a three-phase system. The open style design facilitates easy installation and maintenance.
Key features include:
- Rated for 65A current and 40HP at 480VAC
- Control circuit voltage of 48VAC at 50/60Hz
- Open style construction for straightforward mounting
Designed to withstand vibrations and shocks, it has a mechanical durability of 6 million cycles and an operational life expectancy of 20 years. The device supports a maximum motor phase current of 65A and features a control circuit type compatible with AC 50/60Hz.
Technical Specifications
| Complementary Attributes - Control Circuit Type | AC 50/60 Hz, AC 50/60 Hz |
| Complementary Attributes - Control Circuit Voltage Limits | 0.3...0.6 Uc (-40-70 °C):drop-out AC 50/60 Hz, 0.8...1.1 Uc (-40-60 °C):operational AC 50 Hz, 0.85...1.1 Uc (-40-60 °C):operational AC 60 Hz, 1...1.1 Uc (60-70 °C):operational AC 50/60 Hz |
| Complementary Attributes - Irms Rated Making Capacity | 140 A AC for signalling circuit conforming to IEC 60947-5-1, 250 A DC for signalling circuit conforming to IEC 60947-5-1, 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Complementary Attributes - Maximum Horse Power Rating | 20 hp at 230/240 V AC 50/60 Hz for 3 phase motors, 40 hp at 460/480 V AC 50/60 Hz for 3 phase motors, 5 hp at 115 V AC 50/60 Hz for 1 phase motors, 10 hp at 230/240 V AC 50/60 Hz for 1 phase motors, 20 hp at 200/208 V AC 50/60 Hz for 3 phase motors, 50 hp at 575/600 V AC 50/60 Hz for 3 phase motors |
| Complementary Attributes - Icw Rated Short Time Withstand Current | 640 A 40 °C - 10 s for power circuit, 900 A 40 °C - 1 s for power circuit, 110 A 40 °C - 10 min for power circuit, 260 A 40 °C - 1 min for power circuit, 100 A - 1 s for signalling circuit, 120 A - 500 ms for signalling circuit, 140 A - 100 ms for signalling circuit |
| Complementary Attributes - Ie Rated Operational Current | 80 A (at <60 °C) at <= 440 V AC AC-1 for power circuit, 65 A (at <60 °C) at <= 440 V AC AC-3 for power circuit, 65 A (at <60 °C) at <= 440 V AC AC-3e for power circuit |
| Complementary Attributes - Uc Control Circuit Voltage | 48 V, 48 V AC 50/60 Hz |
| Complementary Attributes - Ue Rated Operational Voltage | power circuit <= 690 V AC 25...400 Hz, power circuit <= 300 V DC |
| Complementary Attributes - Ui Rated Insulation Voltage | signalling circuit 600 V CSA, signalling circuit 600 V UL, power circuit 600 V CSA, power circuit 600 V UL, signalling circuit 690 V IEC 60947-1, power circuit 690 V IEC 60947-4-1 |
| Complementary Attributes - Maximum Motor Phase Current | 65 A |
| Complementary Attributes - Maximum Operating Rate | 3600 cyc/h at 60 °C |
| Complementary Attributes - Minimum Switching Current | 5 mA for signalling circuit |
| Complementary Attributes - Minimum Switching Voltage | 17 V for signalling circuit |
| Complementary Attributes - Rated Breaking Capacity | 1000 A at 440 V for power circuit conforming to IEC 60947 |
| Complementary Attributes - Uimp Rated Impulse Withstand Voltage | 6 kV IEC 60947 |
| Persona Type Ids | EU, LC, OM, OM8, PB, SI |
| Persona Type Names | End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, System Integrator |
| Market Segmentation Id | COMMERCIAL, INDUSTRIAL |
| Market Segmentation | Commercial, Industrial |
| Associated Fuse Rating | 10 A gG for signalling circuit conforming to IEC 60947-5-1, 125 A gG at <= 690 V coordination type 1 for power circuit, 125 A gG at <= 690 V coordination type 2 for power circuit |
| Contactor Application | motor control, resistive load |
| Electrical Durability | 1.4 Mcycles 80 A AC-1 <= 440 V, 1.45 Mcycles 65 A AC-3 <= 440 V, 1.45 Mcycles 50 A AC-3e <= 440 V |
| Hold In Power Consumption In Va | 13-13 VA 60 Hz cos phi 0.3 (at 20 °C), 15-15 VA 50 Hz cos phi 0.3 (at 20 °C) |
| Inrush Power In Va | 140-140 VA 60 Hz cos phi 0.75 (at 20 °C), 160-160 VA 50 Hz cos phi 0.75 (at 20 °C) |
| Insulation Resistance | > 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit, > 10 MOhm for signalling circuit |
| Mechanical Robustness | vibrations contactor open 2 Gn, 5...300 Hz), vibrations contactor closed 4 Gn, 5...300 Hz), shocks contactor closed 15 Gn for 11 ms), shocks contactor open 10 Gn for 11 ms) |
| Motor Power Kw | 30 kW at 380...400 V AC 50/60 Hz (AC-3e), 37 kW at 500 V AC 50/60 Hz (AC-3e), 37 kW at 660...690 V AC 50/60 Hz (AC-3e), 11 kW at 400 V AC 50/60 Hz (AC-4), 18.5 kW at 220...230 V AC 50/60 Hz (AC-3), 30 kW at 380...400 V AC 50/60 Hz (AC-3), 37 kW at 500 V AC 50/60 Hz (AC-3), 37 kW at 660...690 V AC 50/60 Hz (AC-3), 18.5 kW at 220...230 V AC 50/60 Hz (AC-3e) |
| Mounting Support | rail, plate |
| Non Overlap Time | 1.5 ms on de-energisation between NC and NO contact, 1.5 ms on energisation between NC and NO contact |
| Operating Time | 4...19 ms opening, 12...26 ms closing |
| Power Dissipation Per Pole | 9.6 W AC-1, 6.3 W AC-3, 6.3 W AC-3e |
| Range | TeSys, TeSys Deca |
| Safety Reliability Level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1, B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Tightening Torque | power circuit 8 N.m EverLink BTR screw connectors 25-35 mm² hexagonal 4 mm, power circuit 5 N.m EverLink BTR screw connectors 2.5-25 mm² hexagonal 4 mm, control circuit 1.7 N.m EverLink BTR screw connectors pozidriv No 2, power circuit 2.5 N.m EverLink BTR screw connectors pozidriv No 2 |
| Utilisation Category | AC-4, AC-1, AC-3, AC-3e |
Product Documents
Reviews: 0
There are no reviews for this product.
Questions: 0
No questions about this product.
Similar products

Spec Sheet