Model:
8 AWG TelcoFlex II KS24194 L2
SKU:
TF28-FT
Availability:
In Stock
1
  0 reviews

Cut to length - sold by the foot. Enter the desired footage in the QTY box.
Minimum 1' to maximum 1000'. Please call for different colors or longer put ups.

Applications:
TelcoFlex® II Central Office Power Wire and Cable Class I Flexible Tinned Strand Without Braid. The Cable has low-smoke, lead-free and silicone-free non-halogenated insulation. UL Central Office Power Cable 105ºC dry, 60ºC wet. UL Listed RHH/LS FT4 and VW-1, 90ºC dry, 60ºC wet, 600 volts. Sizes 1/0 and larger are UL, CT USE rated. CSA AWM I B 105ºC, 600 volts.

Specifications:
Meets or exceeds the following:
UL Listed As: Central Office Power Cable
UL Listed Standard 44: Thermoset Insulated Type RHH/ST1
FT-4 Flame Test
VW-1
ASTM B-33 and B172 for Flexible Strand
Physical and Electrical tests in accordance with UL Standard 44 Requirements
CSA AWM I B 105ºC
GR - 347 - Core Compliant by Telcordia
Meets the Requirements of WP93811 for Cold Flow (Creep) and Cut Through
Non-Halogen
Low Smoke - LS
IEC 60674 and 60332
RoHS / Reach Compliant

Construction:
Southwire's TelcoFlex ® II Cable is single conductor with a class I (modified) bunched (8 and 6 AWG) and rope-bunched (4 AWG and larger) stranded tinned copper conforming to ASTM B-33 and Underwriter's Laboratories requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping. Insulation is 90ºC rated low smoke, non-halogen, TelcoHyde™ 5221 conforming to Underwriter's Laboratories Standard 44 and Telcordia Specification GR-347-CORE, also UL and CSA 105ºC AWM rated. The insulation has a limiting oxygen index of 35%.

Conductors:
Class I modified bunched (8 and 6 AWG) or rope-bunched (4 AWG and larger) stranded tin-coated copper conforming to ASTM B-33 and Underwriters' Laboratories Requirements. An opaque mylar tape shall be applied over the conductor to facilitate stripping.

Insulation:
90ºC / 105ºC rated low smoke, non-halogen TelcoHyde™ 5221 conforming to Underwriters' Laboratories Standard 44, Subjects 509 and 758, and CSA C22.2 No. 210.2 M90. In addition, TelcoHyde™ 5221 complies with the requirements of Telcordia Specification GR-347-CORE. The insulation has a limiting oxygen index of 35%.

Surface Marking:
Two sides of the cable shall be printed using an ink of a contrasting color and with the following information: "SOUTHWIRE TELCOFLEX (R) II/ KS24194 (TM) L2 NON-HAL (UL) E18321 _ AWG 600 VOLTS RHH ST1 FT4 OR AWM 3578 60(D)C WET VW-1 --- LL8825 CSA AWM I B 105(D)C 600 VOLTS FT4-ST1 YEAR TIME JULIAN DATE --- MEETS IEC INCLUDING 60674 & 60332 SEQUENTIAL FOOTAGE MARKS"
Add "FOR CT USE" before "(UL)" on Sizes 1/0 AWG and larger. Sequential footage markings shall be applied at 2 foot intervals on one side of the cable. "SOUTHWIRE manufacturing order number.

Specifications*:

Size: 8 AWG
Conductor Strand: 41/.0201
Insulation Thickness: 0.060 inches
Outside Diameter: 0.274 inches
Weight: 0.086 lbs per ft
Max. D.C. Res. @ 20ºC: .6790

*Data provided on this page is subject to change based on different manufacturers variances.

Reviews: 0

There are no reviews for this product.

Questions: 0

No questions about this product.

Similar products