Check end-of-line voltage, power loss and cable resistance.
← All Paging & Emergency Audio toolsInputs changed. Calculate again to update the estimate.
Z = V² / tap watts; loop R = 2 × length × conductor resistance / 1,000; load V = V × Z / (Z + loop R).
All speaker load is modeled at the far end, with nominal resistive transformer impedance. Default resistance is approximately 16 AWG copper at 20°C; replace with your cable data and operating temperature. Not a transformer, amplifier or fire-circuit certification.
Manufacturer reference ↗Planning estimates support equipment selection. Final design, equipment ratings and site-specific requirements must be verified before installation.