Prysmian Airguard Cable, 2 AWG 3 Conductor Type MV-105, 15kV, 133%, Medium Voltage Cable
SKU:
PAC23C15kv-FT
Availability:
In Stock
  0 reviews

Prysmian Airguard Cable, 2 AWG 3 Conductor Type MV-105, 15kV, 133%, Medium Voltage Cable

Cut to length - sold by the foot. Enter the desired footage in the QTY box.

Minimum 10' to maximum 5000'. Please call for longer put ups.

Description:
Three conductor cable with stranded copper conductors, extruded insulation system consisting of a thermosetting semiconducting conductor shield, high dielectric strength EPROTENAX™ EPR insulation, thermosetting semiconducting insulation shield, helically applied bare copper tape shield, cabled with fillers and grounding conductors, overall binder tape, foamed polymeric layer for superior mechanical protection, longitudinally applied aluminum tape, extruded oil and hydrocarbon resistant polymeric layer, and overall sunlight resistant PVC jacket. Suitable for Class I Division 2 locations

Application & Benefits:
Prysmian’s patented AIRGUARD™ cable is a direct replacement for continuously corrugated and welded aluminum armored cables (*in Class 1 Div 2 locations or if installed with cables rated 1000V or greater) with 5X the impact performance and 2X-3X the sidewall bearing pressure limit (@ 3000 lbs per rad-ft) This enables longer pulls than with Continuously Corrugated and Welded type cables.

Conductors:
Class B Compact concentric strand soft drawn annealed copper per ASTM

Insulation:
Natural high dielectric strength EPR-based insulation, combined with other materials and agents that enhance the electrical and mechanical characteristics assuring extended cable life.

Conductor Shield:
Extruded thermosetting semiconducting shield which is free stripping from the conductor and bonded to the insulation.

Insulation Shield:
Extruded thermosetting semiconducting shield with controlled adhesion to the insulation providing the required balance between electrical integrity and ease of stripping.

Metalic Shield:
Helically applied non-magnetic copper tape(s) over the insulation shield with a minimum overlap of 15%. A Mylar ribbon is longitudinally applied under the copper tape shield for phase identification -1C w/Red, 1C w/Blue, and 1C w/Black.

Grounding Conductors:
Bare Stranded copper conductor, one in each interstice, per UL, ICEA, and ASTM.

Assembly:
Phase identified shielded conductors cabled with fillers and grounding conductors (as specified), forming a firm and cylindrical cable core. A binder tape is applied to maintain core symmetry and mechanical stability.

Mechanical Protection:
High strength and high crush resistant Airbag Layer extruded over the core assembly.

Chemical Protection:
A layer of Drylam which consists of aluminum tape and a chemical resistant extruded polymer layer is applied.

Jacket:
Sunlight resistant polyvinyl chloride (PVC) jacket.

Standards:
ICEA S-93-639/NEMA WC74 Type MV 105 UL 1072 For CT USE, Direct Buried, Sunlight Resistant, IEEE 383 Flame Test IEEE 1202 Flame Test ICEA T-29-520 at 210,000 BTU/hr MSHA Type MP

Specifications*:

Size: 2 AWG
Insulation Thickness: 220 mils
Number of Ground Wires: 3
Size of Ground Wires: 10 AWG
Conductor Diameter: 0.269 inches
Insulation Diameter: 0.740 inches
Insulation Shield Diameter: 0.790 inches
Overall Jacket Diameter: 2.210 inches
Cable Weight: 3.203 lbs per ft
Minumum Bend Radius: 16 inches
Ampacity: 105C in Duct = 160 amps - In air = 185 amps

Spec Sheet

Belden 8770 Spec SheetView Spec Sheet for Complete Details