Features

  • Built-In Support for Upto 99 SK Detectors and 99 SK Modules, Expandable to 396 SK Detectors and 396 SK Modules Creating a Total Point Capacity of 792 Points Using the SK Protocol (Version 10.0 and Higher)
  • Built-In Support for Upto Any Combination of 12 7 SD Devices, Expandable to 508 Devices Using the SD Protocol
  • Built-In Digital Communicator/Dialer
  • Uses Standard Wire No Shielded or Twisted Pair Required
  • Six Flexput Circuits Configurable as Three Class a (Style Z) or Six Class B (Style Y), Auxiliaryfor Resettable, Constant, or Door Holder Power
  • Can also Be Configured as Input Point to Monitor Conventional Devices
  • Point Status Meets Calibrated Smoke Test Requirements for NFPA 72
  • One Form C Trouble Relay and Two Form C Programmable Relays
  • Built-ISynchronization for Multiple Notification Appliance Manufactures
  • RS-485 SBUS Provides Communication to Intelligent Distributed System Accessories

Tech Info

UL, NFPA 13/15/16/70/72, FM

Technical

UNSPSC Code
46171600