Why Install Electrical Wiring in Conduits?
Installing electrical wiring in conduits (pipes) provides significant benefits such as:
- Mechanical protection for cables and conductors
- Fire safety in combustible or demanding environments
- Shielding from moisture, dust, or UV exposure
In both residential and industrial settings, conduits help maintain NEC-compliant (National Electrical Code) installations, especially when cables require enhanced protection and easy future replacement.
1. General Rules and Requirements
- Spacing from Other Services
- Maintain at least 1.5 ft (0.5 m) from heating lines when crossing perpendicularly
- Keep at least 3.3 ft (1 m) if running parallel to piping for steam or hot water
- Drainage Slope
- Install conduits with a slight incline to allow condensation or minor water infiltration to drain out
- No Cable Splices Inside Conduits
- Conductor splices must be accessible in junction boxes, not hidden in the conduit run
- Pulling and Replacement
- Leave adequate conduit space (avoid “jamming” with wires)
- Keep continuous conduit lengths within practical pulling distances:
- Up to 165 ft (50 m) with one bend
- Up to 130 ft (40 m) with two bends
- Up to 65 ft (20 m) with three bends
Proper planning ensures the conduit route allows easier wire feeding and future cable replacement.
2. Conduit Types and Materials
Electrical conduits generally come in two main material categories:
2.1 Metal Conduits
- Rigid Metal Conduit (RMC): Thick-walled steel or galvanized conduit offering maximum mechanical and fire protection
- Intermediate Metal Conduit (IMC): Lighter than RMC but still robust
- Electrical Metallic Tubing (EMT): Thin-walled steel, suitable for non-combustible buildings and many indoor applications
Metal conduits are mandatory in certain fire-rated or high-risk settings, such as:
- Wood-framed structures where concealed wiring must be protected from ignition
- Flammable or explosive environments requiring heavy-duty, sealed connections
They also provide excellent rodent-proofing and mechanical durability.
2.2 Plastic (PVC) Conduits
- Rigid PVC: Lightweight, corrosion-resistant, typically used for underground or outdoor runs
- Flexible Corrugated Tubing (ENT): Easier to route around corners, but limited mechanical protection
Plastic conduits may be used on non-combustible walls or ceilings to reduce cost and simplify installation. However, metal remains the recommended choice where fire or rodent protection is a priority.
3. Temperature and Current Capacity Considerations
Enclosing wires inside conduits can reduce heat dissipation. Multiple conductors in a single conduit can also elevate internal temperatures. When selecting wire gauge (AWG), consider:
- NEC ampacity derating tables for conduits with multiple conductors
- Ambient temperature and thermal insulation around the conduit
Always confirm your conductor sizes and circuit breakers match local code requirements.
4. Installation Methods and Steps
4.1 Surface (Exposed) Conduit Mounting
- Layout and Marking
- Plan the conduit path to minimize bends and keep pulling distances manageable
- Attach Conduit Supports
- Secure conduits with clamps, straps, or clips, typically every 8–10 ft (2.5–3 m) for straight runs
- Place additional supports within 4–8 inches (100–200 mm) on each side of a bend
- Cutting and Bending
- For metal conduits, use a conduit bender or specialized fittings
- Avoid kinks or flattening the pipe
- Maintain a bend radius of 4–6 times the conduit’s outer diameter
- Join and Seal
- For metal: Use threaded or compression fittings.
- For PVC: Apply solvent welding or use gasketed couplings for watertightness.
- Pull and Secure Wires
- Only after the conduit system is fully in place and any sealants have cured
- Use pulling lubricants if needed, while ensuring no splices occur within the conduit itself
4.2 Concealed Conduit in Walls or Ceilings
- Cut or Chase Channels
- In masonry, cut shallow grooves that accommodate the conduit’s diameter
- In drywall or wood framing, run conduits behind removable panels if possible (for future access)
- Anchor Conduit
- Use clamps or saddles rated for hidden installations
- Consider Expansion
- Allow slight movement for thermal expansion, especially in unheated or outdoor areas
4.3 Conduit Under Concrete Slabs or Within Floor Screed
- Secure conduits firmly to the subfloor or rebar mesh
- Avoid unnecessary bends; keep lines accessible where possible
- Comply with minimum coverage thickness (2–3 inches of concrete over the top of the conduit)
5. Fastening and Joining Methods
- Metal Conduit Connections
- Threaded couplings, compression fittings, or clamp-type couplings
- Coat steel conduits for corrosion protection, or buy galvanized for damp or outdoor spaces
- PVC Conduit Connections
- Solvent-weld bonding (cement) or gasketed fittings for watertight connections
- Check expansion couplings for temperature fluctuation—1/4 inch expansion per 10 ft at about 50 °F temperature changes
Make sure all connections in wet, dusty, or explosive locations are sealed and rated according to the environment’s classification.
6. Common Installation Pitfalls
- Overfilling Conduits
- Crowded cables make pulling difficult and reduce heat dissipation
- Follow NEC’s fill tables for max conductor count
- Excessive Bends
- Too many 90° bends hamper cable pulling and future replacements
- Plan a route that keeps the number of bends at three or fewer per run
- Insufficient Support
- Long, unsupported spans lead to sagging or conduit damage
- Always use recommended brackets within code-defined intervals
- Ignoring Fire Safety
- In wood-framed or flammable structures, using metal conduit (or raceways) may be mandatory
- Check local code requirements before opting for PVC or ENT in concealed spaces
7. Achieving a Safe, Efficient Conduit System
When properly installed, conduit wiring delivers excellent longevity, enhanced fire safety, and mechanical protection compared to open or cable-only systems. Key points for success include:
- Plan conduit runs to minimize bends and maximize accessibility
- Choose the right material (metal vs. plastic) based on code, environment, and mechanical needs
- Maintain code-required distances from hot surfaces and ensure conduits allow drainage
- Ensure correct conductor sizing and fill to handle heat and avoid voltage drop
Why Rely on SafSale.com for Conduit Solutions?
At safsale.com, we supply UL-listed conduits, fittings, and accessories to ensure code-compliant projects across the USA. Our product range covers:
- Steel, IMC, and EMT conduits in various sizes
- PVC and flexible ENT with matching couplings
- High-quality anchors, clamps, and support hardware
- Expert guidance to help you select and install the ideal conduit system
With safsale.com products and support, you’ll streamline your conduit installation and uphold the strict safety standards expected in modern electrical work.
Conclusion
Installing electrical wiring in conduits is a practical, reliable, and often code-required solution for safeguarding cables from mechanical damage, moisture, and fire risk. By carefully selecting conduit materials, support methods, and fill allowances, you’ll secure a system that remains serviceable and future-proof for many years.
Whether running conduit on walls, behind ceilings, or beneath floors, remember to:
- Follow NEC guidelines for conductor fill, bend limitations, and fire safety
- Use proper sealing and bracketing to accommodate temperature changes and environmental conditions
- Plan for maintenance and potential cable replacements by allowing accessible pull points and minimal bends