The Square D ATV630 is a 55kW (75HP) variable speed drive suitable for controlling asynchronous and synchronous motors in industrial environments. It offers advanced communication options including Ethernet, Modbus serial, and Modbus TCP, ensuring seamless integration into automation systems.
Constructed with a sheet steel enclosure, it is wall-mounted and designed for vertical operation within a tolerance of plus or minus 10 degrees. The drive features integrated EMC filters conforming to IEC 61800-3 category C3, and supports multiple protocols for flexible management and control.
- Maximum motor power rating of 55 kW (normal duty) and 45 kW (heavy duty)
- Rated operational voltage of 380 to 480V, three-phase
- Power dissipation of 131 W in natural convection and 917 W in forced convection
- Maximum input current of 97.2 A at 380V and 84.2 A at 480V
- Maximum output frequency of 500 kHz and voltage of 480V
- Supports optional communication modules including Profibus DP V1, PROFINET, DeviceNet, and CANopen
- Designed with safety features including safe torque off (SIL 3) and thermal protections
This drive is suitable for process and utility applications, with a typical lifespan of approximately 10 years. It is compliant with multiple standards including UL 508C, IEC 61800-3, IEC 61508, and conforms to environmental and EMC regulations.
Technical Specifications
| Communications & Management Attributes - Communication Port Protocol | Ethernet, Modbus serial, Modbus TCP |
| Conformance Attributes - Product Certifications | CSA, UL, DNV-GL, ATEX INERIS, ATEX zone 2/22, TÜV |
| Conformance Attributes - Standards | UL 508C, IEC 61800-3, IEC 61800-3 environment 1 category C2, EN/IEC 61800-3 environment 2 category C3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, UL 508C, IEC 61800-3, environment 1 category C2 IEC 61800-3, environment 2 category C3 IEC 61800-3, IEC 61800-5-1, IEC 61000-3-12, IEC 60721-3, IEC 61508, IEC 13849-1 |
| Complementary Attributes - Maximum Horse Power Rating | 75 hp normal duty, 60 hp heavy duty |
| Complementary Attributes - Maximum Switching Current | relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC, relay output R1, R2, R3 resistive, cos phi = 1 3 A 250 V AC, relay output R1, R2, R3 resistive, cos phi = 1 3 A 30 V DC, relay output R1, R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC |
| Complementary Attributes - Maximum Thdi | <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12, <48 % from 80...100 % of load IEC 61000-3-12 |
| Complementary Attributes - Maximum Transient Current | 116.6 A 60 s normal duty), 132 A 60 s heavy duty) |
| Complementary Attributes - Ue Rated Operational Voltage | 380...480 V 55 kW 75 hp normal duty, 380...480 V 45 kW 60 hp heavy duty |
| Complementary Attributes - Us Rated Supply Voltage | 380...480 V, 380...480 V - 15...10 % |
| Complementary Attributes - Brake Chopper Integrated | false |
| Complementary Attributes - Maximum Associated Fuse Rating | 160.0 A |
| Complementary Attributes - Maximum Input Current Per Phase | 97.2 A |
| Complementary Attributes - Maximum Output Frequency | 500 kHz |
| Complementary Attributes - Maximum Output Voltage | 480.0 V |
| Complementary Attributes - Minimum Switching Current | relay output R1, R2, R3 5 mA 24 V DC |
| Complementary Attributes - Maximum Acceleration Under Shock Impact During Operation | 150 m/s² at 11 ms |
| Complementary Attributes - Maximum Acceleration Under Shock Load During Storage | 150 m/s² at 11 ms |
| Complementary Attributes - Maximum Acceleration Under Shock Load During Transport | 150 m/s² at 11 ms |
| Complementary Attributes - Maximum Acceleration Under Vibrational Stress During Operation | 10 m/s² at 13...200 Hz |
| Complementary Attributes - Maximum Acceleration Under Vibratory Load During Storage | 10 m/s² at 13...200 Hz |
| Complementary Attributes - Maximum Acceleration Under Vibratory Load During Transport | 10 m/s² at 13...200 Hz |
| Complementary Attributes - Maximum Deflection Under Vibratory Load During Operation | 1.5 mm at 2...13 Hz |
| Complementary Attributes - Maximum Deflection Under Vibratory Load During Storage | 1.5 mm at 2...13 Hz |
| Complementary Attributes - Maximum Deflection Under Vibratory Load During Transport | 1.5 mm at 2...13 Hz |
| Product Contributes To Saved And Avoided Emissions | YES_SSI2, Yes |
| Persona Type Ids | EU, OM, OM8, SI |
| Persona Type Names | End User, Original Equipment Manufacturer, OEM - Control Panelbuilder, System Integrator |
| Apparent Power | 70 kVA 480 V normal duty), 59.7 kVA 480 V heavy duty) |
| Asynchronous Motor Control Profile | constant torque standard, optimized torque mode, variable torque standard |
| Connector Type | RJ45 on the remote graphic terminal)Ethernet/Modbus TCP, RJ45 on the remote graphic terminal)Modbus serial |
| Discrete And Process Manufacturing | food and beverage processing pump, food and beverage processing fan, water and waste water electro submersible pump (ESP), water and waste water screw compressor, water and waste water compressor centrifugal, water and waste water fan, building - HVAC compressor centrifugal, food and beverage processing other application, mining mineral and metal fan, mining mineral and metal pump, oil and gas fan, water and waste water other application, building - HVAC screw compressor, food and beverage processing atomization, oil and gas electro submersible pump (ESP), oil and gas water injection pump, oil |
| Electrical Connection | control removable screw terminals 0.5...1.5 mm² AWG 20...AWG 16, line side screw terminal 70...120 mm² AWG 1/0...250 kcmil, motor screw terminal 70...120 mm² AWG 1/0...250 kcmil |
| Electromagnetic Compatibility | electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2, radiated radio-frequency electromagnetic field immunity test level 3 conforming to IEC 61000-4-3, electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4, 1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5, conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6 |
| Frequency Resolution | display unit 0.1 Hz, analog input 0.012/50 Hz |
| Insulation Resistance | > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth, > 1 MOhm 500 V DC for 1 minute to earth |