6 KVA Uninterruptible Power Supply - 480 V 1-Phase Input - 120 V Output - Online Double Conversion - NEMA 1 is a product intended for professional commercial and industrial applications.

Key Specifications

  • Unit Type: Uninterruptible Power Supply - True Online Double-Conversion UPS
  • Dimensions: 13.8" W × 29.9" D × 27.8" H
  • Weight: 298 lbs (135.2 kg)
  • Input Voltage: 480V
  • Input Factor: > 0.98 Lagging
  • Reflected Current THD: 4% typ @100% load
  • 7% typ @50% load
  • Output Voltage: 120V
  • Voltage Regulation: ±2%
  • Voltage THD: <2.5% at 100% linear load
  • Transient Response: ±5%

This item is grouped with Data Center Uninterruptible Power Supply (UPS).

Before ordering: Verify ratings, dimensions, compatibility, and installation requirements before ordering.

Specifications

@ 100% Load
91.2%
@ 50% Load
90.6%
@ 75% Load
91.3%
Altitude
0 to 3,300 ft (1,006 m) without derating
Battery Type
VRLA (Sealed Lead Acid)
Battery Type Options
Sealed Lead Acid (VRLA), Maintenance-Free / Lithium Iron Phosphate (LiFePO₄ / LFP)
Color
Black
Communications
Supports SNMP / Web / Modbus / BACnet (via communication card, per model configuration)
Cooling
Forced Air
Dimensions
13.8" W × 29.9" D × 27.8" H
Enclosure
NEMA 1 (Indoor)
Float Voltage
245 VDC
Frequency
50/60 Hz
Frequency Regulation
±0.05% in free running mode
Heat Rejection @ 100% Load
1.4 kBTU/hr
Input Factor
> 0.98 Lagging
Internal Batteries
Included
Maximum Tower Width (with batteries & accessories)
≤ 500 mm
Minimum Voltage
173 VDC
Mounting Configuration
Tower
Nominal Voltage
216 VDC
Operating Temperature
32°F to 104°F (0°C to 40°C)
Output Power Capacity
6,000 VA (6 kVA)
Output Power Factor
0.70
Output Voltage
120V
Overload Capacity
105%–150% for 1 minute
Phase Displacement
1° for 100% balanced load
Reflected Current THD
4% typ @100% load; 7% typ @50% load
Relative Humidity
30% to 90% Non-Condensing
Technology
True On-Line Double Conversion (Transformer-less, IGBT-Based)
Transient Recovery Time
50 ms
Transient Response
±5%
Unit Type
Uninterruptible Power Supply - True Online Double-Conversion UPS
Voltage Regulation
±2%
Voltage THD
<2.5% at 100% linear load
Warranty Limitations
Included with Bid Submission
Weight
298 lbs (135.2 kg)

Technical

Input Voltage
480V
Location