The AL800LGK9E Logic Board terminal connects to the 24VDC FACP notification appliance circuit outputs. It supports Class A, Style Z or Class B, Style W, X, Y inputs. Input trigger voltage is 8-33VDC @ 5mA min. Terminal polarity indicates alarm condition. During an alarm condition, selected outputs drive notification appliances based on output switches [OUT1 through OUT4]. A trouble condition on an output loop will cause the corresponding input to trip the FACP by opening the FACP loop. An alarm condition overrides trouble to drive notification appliances.