The Square D regulated power supply converts 100-240V AC to a stable 24V DC output, supporting applications requiring up to 1.2A of current. Its modular design allows for versatile mounting options including DIN rail and panel mounting, making it suitable for control panels and automation systems.
Constructed with a durable plastic enclosure, it features a dielectric strength of 3000 V AC and a total lifecycle of approximately 10 years under normal operating conditions. The power supply includes protections against overload, short circuits, over temperature, and overvoltage, with automatic or manual reset functionalities.
- Input Voltage: 100-240 V AC single phase
- Output Voltage: 24 V DC, limits between 24 and 28 V
- Output Current: 1.2 A
- Rated Power: 30 W
- Efficiency: 87% at 115 V AC and 87% at 230 V AC
- Residual Ripple: Less than 100 mV
- Protection: Against overload, short-circuits, over temperature, and overvoltage
- Mounting Support: DIN rail, panel mounting, top hat type TH35-15 and TH35-7.5 rails
This power supply complies with CE, cUL, RCM, CB Scheme, EAC, KC, and NEC class 2 standards, and features a high vibration resistance of 3 mm (f= 2-9 Hz) and 10 m/s² (f= 9-200 Hz). It has a service life of approximately 10 years and a total lifecycle carbon footprint of 217 kg CO2 equivalent.
Technical Specifications
| Complementary Attributes - Maximum Leakage Current | 0.25 mA 240 V AC |
| Complementary Attributes - Rated Power In W | 30 W |
| Persona Type Ids | EU, OM, OM8 |
| Persona Type Names | End User, Original Equipment Manufacturer, OEM - Control Panelbuilder |
| Current Consumption | < 0.8 A 115 V AC, < 0.8 A 115 V AC, < 0.8 A 115 V AC, < 0.6 A 230 V AC, < 0.6 A 230 V AC, < 0.6 A 230 V AC, < 0.8 A 115 V AC, < 0.8 A 115 V AC, < 0.8 A 115 V AC, < 0.6 A 230 V AC, < 0.6 A 230 V AC |
| Earthing System | TN, TT, IT |
| Efficiency | 87 % 115 V AC, 87 % 230 V AC |
| Electromagnetic Compatibility | immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2, immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2, electromagnetic field immunity test - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3, immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4, |
| Electromagnetic Emission | conducted emissions IEC 61000-6-3, radiated emissions IEC 61000-6-4 |
| Holding Time | > 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC |
| Inrush Current | 25 A 115 V, 50 A 230 V |
| Line And Load Regulation | < 0.5 % network in line, < 0.5 % network in line, < 1 % network 0 to 100 % load, < 1 % network 0 to 100 % load, < 0.5 % network in line, < 0.5 % network in line, < 1 % network 0 to 100 % load, < 1 % network 0 to 100 % load |
| Mounting Support | top hat type TH35-15 rail IEC 60715, top hat type TH35-7.5 rail IEC 60715, double-profile DIN rail, panel mounting |
| Power Factor | 0.48 at 115 V AC, 0.38 at 230 V AC |
| Supply | SELV IEC 60950-1, SELV IEC 60204-1, SELV IEC 60364-4-41 |
| Vibration Resistance | 3 mm (f= 2-9 Hz) conforming to IEC 60721-3-3, 10 m/s² (f= 9-200 Hz) conforming to IEC 60721-3-3 |
| Connections Terminals | screw connection 0.5...1.5 mm², AWG 20...AWG 16) without wire end ferrule input/output, screw connection 0.5...1 mm², AWG 20...AWG 18) with wire end ferrule input/output |
| Meantime Between Failure Mtbf | 2500000 h at 25 °C, full load, 1000000 h at 55 °C, 80 % load |
| Carbon Footprint Of The Distribution Phase A4 | 0.0221921951, 0 kg CO2 eq. |
| Carbon Footprint Of The End Of Life Phase C1 To C4 | 0.1479769903, 0.1 kg CO2 eq. |
| Carbon Footprint Of The Installation Phase A5 | 0 kg CO2 eq., 0.0017612388 |
| Carbon Footprint Of The Manufacturing Phase A1 To A3 | 2 kg CO2 eq., 2.4269967786 |
| Carbon Footprint Of The Use Phase B2 B3 B4 B6 | 215 kg CO2 eq., 214.6 |
| Certificate Agency | CE, cUL Listed, cUL Recognized, RCM, CB Scheme, EAC, KC, NEC class 2 |
| Other Technical Guide | https://download.schneider-electric.com/files?p_Doc_Ref=ESXP1G003EN&p_File_name=ESXP1G003EN_web.pdf, ESXP1G003EN |
| Local Data Status | Publishable |
| Local Publishable Date | 2026-03-26 |
| Return Indicator | Y |
| Stocking Flag | Y |
| Stock Policy | 1 |
| Device Type | PLC System - PLC Component |
| Serviceability | No |
| Traceability | Yes |
| Field Service Division | IDIBS |
| Service Catalog Item | Finished good |
Product Documents