The Square D regulated power supply is designed to deliver a stable 24V DC output with a maximum current of 2.5A, suitable for control circuits and automation systems. Its modular design allows for flexible installation in various environments.
Constructed with a durable plastic enclosure, it features a dielectric strength of 3000 V AC and supports mounting on top hat type TH35-15 rail, double-profile DIN rail, or panel mounting. The device operates within a voltage range of 100 to 240 V AC at a frequency of 50-60 Hz.
- Output Voltage: 24 V DC
- Output Current: 2.5 A
- Input Voltage: 100-240 V AC single phase
- Efficiency: 90% at full load
- Power Dissipation: 6.5 W
- Enclosure Material: Plastic
- Dielectric Strength: 3000 V AC
- Vibration Resistance: 3 mm (2-9 Hz), 10 m/s² (9-200 Hz)
- Shock Resistance: 150 m/s² for 11 ms
- Protection Class: Class II without PE connection
This power supply features protection against overload, short circuits, over temperature, and overvoltage with automatic or manual reset options. It is compliant with multiple safety and environmental standards, including CE and cUL recognition.
Technical Specifications
| Complementary Attributes - Maximum Leakage Current | 0.25 mA 240 V AC |
| Complementary Attributes - Rated Power In W | 60 W |
| Persona Type Ids | EU, OM, OM8 |
| Persona Type Names | End User, Original Equipment Manufacturer, OEM - Control Panelbuilder |
| Current Consumption | < 1.5 A 115 V AC, < 1.5 A 115 V AC, < 1.5 A 115 V AC, < 1 A 230 V AC, < 1 A 230 V AC, < 1 A 230 V AC, < 1.5 A 115 V AC, < 1.5 A 115 V AC, < 1.5 A 115 V AC, < 1 A 230 V AC, < 1 A 230 V AC |
| Earthing System | TN, TT, IT |
| Efficiency | 90 % 115 V AC, 90 % 230 V AC |
| Electromagnetic Compatibility | immunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2, immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2, electromagnetic field immunity test - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3, electromagnetic field immunity test - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3, immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000-4-4, |
| Electromagnetic Emission | conducted emissions IEC 61000-6-3, radiated emissions IEC 61000-6-4 |
| Holding Time | > 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 60 ms 230 V AC, > 60 ms 230 V AC |
| Inrush Current | 30 A 115 V, 60 A 230 V |
| Line And Load Regulation | < 0.5 % network in line, < 0.5 % network in line, < 1 % network 0 to 100 % load, < 1 % network 0 to 100 % load, < 0.5 % network in line, < 0.5 % network in line, < 1 % network 0 to 100 % load, < 1 % network 0 to 100 % load |
| Mounting Support | top hat type TH35-15 rail IEC 60715, top hat type TH35-7.5 rail IEC 60715, double-profile DIN rail, panel mounting |
| Power Factor | 0.50 at 115 V AC, 0.39 at 230 V AC |
| Supply | SELV IEC 60950-1, SELV IEC 60204-1, SELV IEC 60364-4-41 |
| Vibration Resistance | 3 mm (f= 2-9 Hz) conforming to IEC 60721-3-3, 10 m/s² (f= 9-200 Hz) conforming to IEC 60721-3-3 |
| Connections Terminals | screw connection 0.5...2.5 mm², AWG 20...AWG 14) without wire end ferrule output, screw connection 0.5...1.5 mm², AWG 20...AWG 16) with wire end ferrule output, screw connection 0.5...1.5 mm², AWG 20...AWG 16) input |
| Meantime Between Failure Mtbf | 1300000 h at 25 °C, full load, 700000 h at 55 °C, 80 % load |
| Carbon Footprint Of The Distribution Phase A4 | 0.028037, 0 kg CO2 eq. |
| Carbon Footprint Of The End Of Life Phase C1 To C4 | 0.2 kg CO2 eq., 0.18695 |
| Carbon Footprint Of The Installation Phase A5 | 0.0022251, 0 kg CO2 eq. |
| Carbon Footprint Of The Manufacturing Phase A1 To A3 | 3 kg CO2 eq., 3.0662 |
| Carbon Footprint Of The Use Phase B2 B3 B4 B6 | 279 kg CO2 eq., 278.98 |
| Certificate Agency | CE, cUL Listed, cUL Recognized, RCM, CB Scheme, EAC, KC, NEC class 2 |
| Other Technical Guide | https://download.schneider-electric.com/files?p_Doc_Ref=ESXP1G003EN&p_File_name=ESXP1G003EN_web.pdf, ESXP1G003EN |
| Local Data Status | Publishable |
| Local Publishable Date | 2026-03-26 |
| Return Indicator | Y |
| Stocking Flag | Y |
| Stock Policy | 1 |
| Device Type | PLC System - PLC Component |
| Serviceability | No |
| Traceability | Yes |
| Field Service Division | IDIBS |
| Manufacturing Carbon Footprint | 3.0662 |