Model:
BMXDDI6402KH
Availability:
In Stock
Documents:
Spec Sheet
$1,004.40
Estimated price. Final price and availability are subject to confirmation. Contact our sales team for a current quote.
  0 reviews

This discrete input module is part of the Modicon X80 series, offering 64 input channels powered by a 24V DC positive supply. It is engineered for use in severe environments and supports operation within a temperature range of -25°C to +70°C (-13°F to 158°F).

Designed for industrial automation, this module reduces spare parts inventory, maintenance, and training costs by providing a unified environment for I/O deployment in automation architectures. It features conformal coating for enhanced durability and an IP20 rating for protection against dust and other particles.

  • Number of inputs: 64 isolated channels
  • Supply voltage: 24V DC positive
  • Input current: 0.6 mA at 24 V DC
  • Input impedance: 40,000 Ohms
  • Voltage detection threshold: 18 V DC sensor OK, > 18 V DC sensor OK
  • Dielectric strength: 1500 V AC for 1 minute between primary and secondary, 500 V DC between channels
  • Environmental resistance: gas, dust, sand, salt, mold, and fungal spores resistant
  • MTBF: 511,375 hours
  • Dimensions: 32 x 100 x 86 mm
  • Weight: 0.145 kg

This module is compatible with Modicon M340 and M580 PLCs, featuring two 40-way connectors and requiring installation on a rack with two screws. It is certified by CE, UL, CSA, RCM, and EAC standards.

Technical Specifications

Complementary Attributes - Dc Maximum Filtering Time7 ms
Persona Type IdsEU, OM8, SI
Persona Type NamesEnd User, OEM - Control Panelbuilder, System Integrator
Dielectric Strength1500 V AC 50/60 Hz 1 minute, primary/secondary, 500 V DC 1 minute, between group of channels
Environmental Characteristicgas resistant class Gx, gas resistant class 3C4, dust resistant class 3S4, sand resistant class 3S4, salt resistant level 2, mold growth resistant class 3B2, fungal spore resistant class 3B2
Insulation Resistance> 10 MOhm 500 V DC, > 10 MOhm 500 V DC, > 10 MOhm 500 V DC, > 10 MOhm 500 V DC
Local Signalling1 LED (green) for +32 channels indicator, 1 LED (green) for module operating (RUN), 1 LED per channel (green) for channel diagnostic, 1 LED (red) for module error (ERR), 1 LED (red) for module I/O
MarkingCE, UKCA, cULus, RCM, EAC
Voltage Detection Threshold< 14 V DC sensor fault, < 14 V DC sensor fault, < 14 V DC sensor fault, < 14 V DC sensor fault, > 18 V DC sensor OK, > 18 V DC sensor OK, > 18 V DC sensor OK, > 18 V DC sensor OK, < 14 V DC sensor fault, < 14 V DC sensor fault, < 14 V DC sensor fault, < 14 V DC sensor fault, > 18 V DC sensor OK, > 18 V DC sensor OK
Voltage State 0 Guaranteed<= 4 V, <= 4 V
Voltage State 1 Guaranteed>= 15 V, >= 15 V
Carbon Footprint Of The Distribution Phase A40.0249758545, 0 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C40.3 kg CO2 eq., 0.3389150303
Carbon Footprint Of The Installation Phase A50.0508592485, 0.1 kg CO2 eq.
Carbon Footprint Of The Manufacturing Phase A1 To A324 kg CO2 eq., 24.4040121212
Carbon Footprint Of The Use Phase B2 B3 B4 B627 kg CO2 eq., 27.1406748603
Certificate AgencyATEX zone 2, IECEx zone 2, CCC Ex zone 2 (pending), cULus HazLoc
Local Data StatusPublishable
Local Publishable Date2026-01-23
Return IndicatorN
Stocking FlagY
Stock Policy1
Device TypePLC System - PLC Component
ServiceabilityNo
TraceabilityYes
Field Service DivisionIDIBS
Average Life Duration20 year(s)
Weee ScopeOut
Weee Product Category5
Scope PerimeterAt least in Europe
Eoli Availability DisplayYes
End Of Life Doc RefENVEOLI2311046EN
Reach Full Compliance StatusReference contains Substances of Very High Concern above the threshold
Reach Full Compliance Status IdCONTAINS_SVHC
Reach Compliance DirectiveReference contains Substances of Very High Concern above the threshold

Product Documents

Reviews: 0

There are no reviews for this product.

Questions: 0

No questions about this product.