The Square D PowerLogic HDPM6000 is a multi-circuit energy measurement device equipped with 126 retrofit modules, calibrated for 60 Hz, 480 V operation. It provides precise measurement of electrical parameters across various circuits, supporting asset management, measurement, and cost management functions.
Key features include:
- Network frequency of 60 Hz
- Rated supply voltage of 24 V DC
- Measurement accuracy of +/- 1%
- Measurement voltage range from 120 V to 480 V AC at 60 Hz
- Sampling rate of 128 samples per cycle
- Memory capacity of 8 GB
- Supports communication protocols such as TCP/IP, Modbus, SNMP, and BACnet
- Compatible with 2P + E, 3P + E, and 3P + N + E pole configurations
- Includes external CT and Rogowski coil analog inputs
- Web services for real-time data viewing and configuration
- Measurement of total harmonic distortion and power quality analysis
- Measurement categories include active, reactive, apparent power, power factor, and frequency
Designed for indoor installation, it mounts via clips or screws on a 35 mm DIN rail or enclosure. The device operates within an ambient air temperature range of -20°C to 60°C and a storage temperature of -40°C to 85°C, with relative humidity levels from 5% to 90%.
Technical Specifications
| Network Frequency | 60 Hz |
| Energy Management | asset management || measurement || cost management |
| [Us] Rated Supply Voltage | 24 V DC |
| Power Quality Analysis | total harmonic distortion |
| Variant | equipped |
| Type Of Measurement | current per channel || current all channels || active energy per channel || active energy all channels || active power per channel || active power all channels || apparent power per channel || apparent power all channels || reactive power per channel || reactive power all channels || frequency || power factor per channel || power factor average |
| Product Or Component Type | multi-circuit energy meter |
| Product Name | PowerLogic HDPM6000 |
| Device Short Name | HDPM6000 |
| Range | PowerLogic |
| Complementary - Communication Port Support | 2 RJ45 Ethernet || RS485 screw block terminal || I/O bus RJ45 |
| Complementary - Measurement Accuracy | +/- 1 % |
| Complementary - Measurement Voltage | 120-120 V AC 60 Hz || 208-208 V AC 60 Hz || 380-380 V AC 60 Hz || 400-400 V AC 60 Hz || 415-415 V AC 60 Hz || 480-480 V AC 60 Hz |
| Complementary - Sampling Rate | 128 samples/cycle |
| Complementary - Memory Capacity | 8 GB |
| Complementary - Communication Port Protocol | TCP/IP || Modbus || SNMP || BACnet |
| Complementary - Poles Description | 2P + E || 3P + E || 3P + N + E |
| Complementary - Analogue Input Type | external CT || Rogowski coil |
| Complementary - Web Services | web page || controller configuration || viewing of captured waveform || real time viewing of data |
| Complementary - Communication Of Data | power quality || reading of measurements || percentage of load |
| Complementary - Provided Equipment | retrofit module 1 84-circuit || retrofit module 1 42-circuit |
| Complementary - Measurement Category | category III |
| Complementary - Noise Level | 0-65 dB |
| Offer Sustainability - China Rohs Regulation | X |
| Offer Sustainability - Rohs Exemption Information | Yes |
| Offer Sustainability - Mercury Free | Yes |
| Offer Sustainability - Eu Rohs Directive | Compliant |
| Offer Sustainability - Reach Regulation | Reference contains Substances of Very High Concern above the threshold |
| Offer Sustainability - California Proposition 65 | WARNING: This product can expose you to chemicals including: Lead and lead compounds, which is known to the State of California to cause cancer and birth defects or other reproductive harm. For more information go to www.P65Warnings.ca.gov |
| Environment - Ambient Air Temperature For Operation | -20-60 °C |
| Environment - Mounting Mode | clipped || by screws |
| Environment - Ambient Air Temperature For Storage | -40-85 °C |
| Environment - Relative Humidity | 5-90 % |
| Environment - Standards | IEC 62443 |
| Environment - Mounting Support | 35 mm DIN rail || enclosure |
Product Documents
For Square D PowerLogic HDPM6000 Multi-Circuit Energy Meter Bundle METSEHDPM6126MC, compare the listed details with project drawings, replacement requirements, and any site-specific electrical or low-voltage conditions.
There are no reviews for this product.
No questions about this product.

Spec Sheet