$176.77
Estimated price. Final price and availability are subject to confirmation. Contact our sales team for a current quote.
The Square D RM35UA11MW multifunction voltage control relay provides reliable monitoring of voltage and electrical values in industrial and building control panels. Its modular design allows for flexible installation on DIN rails, occupying the same space as standard 3-pole DIN devices.
Key features include a selectable memory function, an integral LED indicator for control status, a sealable cover, and simple screw trimmer adjustments for precise settings. It offers automatic shutdown management and fault indication for quick troubleshooting, making it suitable for refurbishing older systems without the need for a PLC.
Technical Specifications
| Complementary Attributes - Ui Rated Insulation Voltage | 250 V IEC 60664-1, 600 V IEC 60664-1 |
| Complementary Attributes - Control Circuit Frequency | 40...70 Hz +/- 10 % |
| Complementary Attributes - Control Circuit Voltage Limits | - 15 % + 10 % Un |
| Complementary Attributes - Line Rated Current | 5 A |
| Complementary Attributes - Maximum Measuring Cycle | 30 ms measurement cycle as true rms value |
| Complementary Attributes - Maximum Power Consumption In W | 0.6 W DC |
| Complementary Attributes - Maximum Switching Current | 5 A AC/DC |
| Complementary Attributes - Maximum Switching Voltage | 250 V AC/DC |
| Complementary Attributes - Minimum Switching Current | 10 mA 5 V DC |
| Complementary Attributes - Uc Control Circuit Voltage | 24...240 V |
| Complementary Attributes - Us Rated Supply Voltage | 24...240 V AC/DC 50/60 Hz, non self-powered |
| Persona Type Ids | BM9, EU, LC, OM, OM8, PB, SC, SI, VR |
| Persona Type Names | Charge Point Operator, End User, Contractor, Original Equipment Manufacturer, OEM - Control Panelbuilder, Panel Builder, Electrician, System Integrator, IT Channel Partner |
| Market Segmentation Id | COMMERCIAL, INDUSTRIAL |
| Market Segmentation | Commercial, Industrial |
| Dielectric Test Voltage | 2 kV AC 50 Hz, 1 min IEC 60255-5, 2 kV AC 50 Hz, 1 min IEC 60664-1 |
| Electromagnetic Compatibility | emission standard for industrial environments conforming to IEC 61000-6-4, emission standard for residential, commercial and light-industrial environments conforming to IEC 61000-6-3, immunity for industrial environments conforming to NF EN/IEC 61000-6-2 |
| Insulation Resistance | > 500 MOhm 500 V DC between supply and relay output IEC 60255-5, > 500 MOhm 500 V DC between supply and relay output IEC 60255-5, > 500 MOhm 500 V DC between supply and relay output IEC 60255-5, > 500 MOhm 500 V DC between supply and relay output IEC 60255-5, > 500 MOhm 500 V DC between supply and relay output IEC 60255-5, > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1, > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1, > 500 MOhm 500 V DC between measurement and relay output IEC 60664-1, > 500 MOhm 500 V DC between measurement and relay output IEC 6066 |
| Local Signalling | LED (green) for power ON, LED (yellow) for relay ON |
| Measurement Error | +/- 0.05 %/°C with temperature variation, +/- 0.05 %/°C with temperature variation, < 1 % over the whole range with voltage variation, < 1 % over the whole range with voltage variation, +/- 0.05 %/°C with temperature variation, +/- 0.05 %/°C with temperature variation, < 1 % over the whole range with voltage variation, < 1 % over the whole range with voltage variation |
| Non Dissipating Shock Wave | 4 kV IEC 60255-5, 4 kV IEC 60664-1, 4 kV IEC 61000-4-5 |
| Operating Rate | <= 360 operations/hour full load, <= 360 operations/hour full load, <= 360 operations/hour full load, <= 360 operations/hour full load |
| Repeat Accuracy | +/- 0.5 % input and measurement circuit, +/- 0.5 % input and measurement circuit, +/- 2 % time delay, +/- 2 % time delay, +/- 0.5 % input and measurement circuit, +/- 0.5 % input and measurement circuit, +/- 2 % time delay, +/- 2 % time delay |
| Resistance Across Terminals | 30 mOhm E2-M terminals, 5 mOhm E1-M terminals, 50 mOhm E3-M terminals |
| Safety Reliability Data | B10d = 290000, MTTFd = 308.2 years |
| Sensitivity Scale | 0.05...0.5 V E1-M terminals, 0.3...3 V E2-M terminals, 0.5...5 V E3-M terminals |
| Utilisation Category | AC-12 IEC 60947-5-1, AC-13 IEC 60947-5-1, AC-14 IEC 60947-5-1, AC-15 IEC 60947-5-1, DC-12 IEC 60947-5-1, DC-13 IEC 60947-5-1, DC-14 IEC 60947-5-1 |
| Vibration Resistance | 0.35 mm (f= 5-57.6 Hz) conforming to IEC 60068-2-6, 1 gn (f= 57.6-150 Hz) conforming to IEC 60255-21-1 |
| Connections Terminals | screw terminals, 1 x 0.5...1 x 4 mm² AWG 20...AWG 11) solid without cable end, screw terminals, 2 x 0.5...2 x 2.5 mm² AWG 20...AWG 14) solid without cable end, screw terminals, 1 x 0.2...2 x 2.5 mm² AWG 24...AWG 12) flexible with cable end, screw terminals, 2 x 0.2...2 x 1.5 mm² AWG 24...AWG 16) flexible with cable end, screw connectors |
| Carbon Footprint Of The Distribution Phase A4 | 0.01830730075625363, 0 kg CO2 eq. |
| Carbon Footprint Of The End Of Life Phase C1 To C4 | 0.3 kg CO2 eq., 0.26282577079697494 |
| Carbon Footprint Of The Installation Phase A5 | 0.04542568353694008, 0 kg CO2 eq. |
| Carbon Footprint Of The Manufacturing Phase A1 To A3 | 9 kg CO2 eq., 9.42719604421175 |
| Carbon Footprint Of The Use Phase B2 B3 B4 B6 | 40 kg CO2 eq., 40.209599999999995 |
| Certificate Agency | GOST, CSA, GL, UL, C-tick |
Product Documents
Reviews: 0
There are no reviews for this product.
Questions: 0
No questions about this product.
Similar products

Spec Sheet