Model:
ABLS1A24050
Availability:
In Stock
Documents:
Spec Sheet
$338.30
Estimated price. Final price and availability are subject to confirmation. Contact our sales team for a current quote.
  0 reviews

The Square D regulated power supply converts 100-240V AC to a stable 24V DC output, supporting up to 5A of current. Its aluminum enclosure ensures durability and effective heat dissipation, making it suitable for industrial environments.

  • Input Voltage: 100-240V AC single phase
  • Output Voltage: 24 V DC
  • Output Current: 5 A
  • Enclosure Material: Aluminum
  • Dielectric Strength: 3000 V AC
  • Mounting Support: Top hat type TH35-15 rail IEC 60715, double-profile DIN rail
  • Power Dissipation: 25 W
  • Efficiency: 85% at 115 V AC, 88% at 230 V AC
  • Power Factor: 0.55 at 115 V AC, 0.45 at 230 V AC
  • Vibration Resistance: 3 mm (2-9 Hz), 10 m/s² (9-200 Hz)
  • Protection: Against overload, short-circuits, over temperature, and overvoltage with manual or automatic reset
  • Response Time: Less than 1 second
  • Service Life: 10 years

Technical Specifications

Complementary Attributes - Maximum Leakage Current1 mA 240 V AC
Complementary Attributes - Rated Power In W120 W
Persona Type IdsEU, OM, OM8
Persona Type NamesEnd User, Original Equipment Manufacturer, OEM - Control Panelbuilder
Current Consumption< 2.5 A 115 V AC, < 2.5 A 115 V AC, < 2.5 A 115 V AC, < 1.4 A 230 V AC, < 1.4 A 230 V AC, < 1.4 A 230 V AC, < 1.3 A 140 V DC, < 1.3 A 140 V DC, < 1.3 A 140 V DC, < 2.5 A 115 V AC, < 2.5 A 115 V AC, < 2.5 A 115 V AC, < 1.4 A 230 V AC, < 1.4 A 230 V AC, < 1.3 A 140 V DC, < 1.3 A 140 V DC, < 1.3 A 140 V DC
Earthing SystemTN, TT, IT
Efficiency85 % 115 V AC, 88 % 230 V AC
Efficiency At Full Load85...264 V AC without temperature derating, 120...375 V DC without temperature derating
Electromagnetic Compatibilityimmunity to electrostatic discharge - test level: 8 kV (contact discharge) conforming to IEC 61000-4-2, immunity to electrostatic discharge - test level: 15 kV (air discharge) conforming to IEC 61000-4-2, immunity to conducted RF disturbances - test level: 15 V/m (80 MHz...2 GHz) conforming to IEC 61000-4-3, immunity to conducted RF disturbances - test level: 5 V/m (2...2.7 GHz) conforming to IEC 61000-4-3, immunity to conducted RF disturbances - test level: 5 V/m (2.7...6 GHz) conforming to IEC 61000-4-3, immunity to fast transients - test level: 4 kV (on input-output) conforming to IEC 61000
Electromagnetic Emissionconducted emissions IEC 61000-6-3, radiated emissions IEC 61000-6-4
Holding Time> 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 40 ms 230 V AC, > 40 ms 230 V AC, > 40 ms 230 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 20 ms 115 V AC, > 40 ms 230 V AC, > 40 ms 230 V AC
Inrush Current30.0 A 115 V, 60.0 A 230 V
Line And Load Regulation< 0.5 % network 0 to 100 % load at 25 °C, < 0.5 % network 0 to 100 % load at 25 °C, < 0.5 % network 0 to 100 % load at 25 °C, < 1 % network full voltage range in line at 25 °C, < 1 % network full voltage range in line at 25 °C, < 1 % network full voltage range in line at 25 °C, < 0.5 % network 0 to 100 % load at 25 °C, < 0.5 % network 0 to 100 % load at 25 °C, < 0.5 % network 0 to 100 % load at 25 °C, < 1 % network full voltage range in line at 25 °C, < 1 % network full voltage range in line at 25 °C
Mounting Supporttop hat type TH35-15 rail IEC 60715, top hat type TH35-7.5 rail IEC 60715, double-profile DIN rail
Power Factor0.55 at 115 V AC, 0.45 at 230 V AC
SupplySELV IEC 60950-1, SELV IEC 60204-1, SELV IEC 60364-4-41
Vibration Resistance3 mm (f= 2-9 Hz) conforming to IEC 60068-2-6, 10 m/s² (f= 9-200 Hz) conforming to IEC 60068-2-6
Connections Terminalsscrew connection 0.75...4 mm², AWG 18...AWG 12) with wire end ferrule input, screw connection 0.5...4 mm², AWG 20...AWG 12) without wire end ferrule output, screw connection 0.5...2.5 mm², AWG 20...AWG 14) with wire end ferrule output, screw connection 0.75...4 mm², AWG 18...AWG 12) without wire end ferrule input
Carbon Footprint Of The Distribution Phase A40.2814372922210785, 0.3 kg CO2 eq.
Carbon Footprint Of The End Of Life Phase C1 To C41.317561161917302, 1 kg CO2 eq.
Carbon Footprint Of The Installation Phase A50 kg CO2 eq., 0.01136038423392367
Carbon Footprint Of The Manufacturing Phase A1 To A37 kg CO2 eq., 6.538260491663987
Carbon Footprint Of The Use Phase B2 B3 B4 B61 243 kg CO2 eq., 1242.774451102273
Certificate AgencyCE, cUL Listed, cUL Recognized, RCM, CB Scheme, EAC, KC
Other Technical Guidehttps://download.schneider-electric.com/files?p_Doc_Ref=ESXP1G003EN&p_File_name=ESXP1G003EN_web.pdf, ESXP1G003EN
Local Data StatusPublishable
Local Publishable Date2026-01-12
Return IndicatorY
Stocking FlagY
Stock Policy1
Device TypePLC System - PLC Component
ServiceabilityNo
TraceabilityYes
Field Service DivisionIDIBS
Weee ScopeIn

Product Documents

Reviews: 0

There are no reviews for this product.

Questions: 0

No questions about this product.